Used in the 10kV, 50Hz three-phase power distribution system for control and protection of power equipment such as transformer, cables, and overhead lines, especially suitable for terminal substations and box-type substations used in urban network and rural network and for control and protection of ring network and dual radiant power supply unit.
No. | Parameter Name | Unit | FZN25-12D | FZRN25-12D | ||
1 | Rated voltage | kV | 12 | 12 | ||
2 | Rated frequency | Hz | 50 | 50 | ||
3 | Rated current | A | 630 | 200 | ||
4 | Rated insulation level | Power frequency withstand voltage for 1 minute | Voltage to ground, Phase-phase voltage | kV | 42 | 42 |
Break voltage | 48 | 48 | ||||
Vacuum break voltage | 30 | 30 | ||||
Lightning impulse withstand voltage (peak) | Voltage to ground, Phase-phase voltage | 75 | 75 | |||
Break voltage | 85 | 85 |
Working environment conditions:
1.1 Ambient temperature: Upper limit: +40ºC; Lower limit: -15ºC;
1.2 The altitude does not exceed 1000m.
1.3 For relative air humidity, the daily mean is not greater than 95%, and the monthly mean is not greater than 90%;
1.4 The earthquake intensity does not exceed 8 degrees.
1.5 Installed in places free of fire, explosive risk, chemical corrosion, and violent vibration.
1.6 The installation site shall be free of flammable substance, explosive risk, chemical corrosion and violent vibration.
FN12-12(D)/T630-20 Indoor High-Voltage Pressure-Operated Loa...
GN19-12(C) indoor high-voltage isolating switch is used in t...
GN30-12(D) indoor high-voltage isolating switch is a new rot...