Three-phase AC 50Hz outdoor high-voltage switchgear, used in the 10kV electrical power systems of rural power grid and urban power grid for opening and closing load current, overload current, and short circuit current, and in other similar applications.
No. | Parameter Name | Unit | Value | |
1 | Rated voltage | kV | 12 | |
2 | Rated current | A | 630、 1250 | |
3 | Rated frequency | Hz | 50 | |
4 | Rated circuit-breaker breaking current | kA | 20 | 25 |
5 | Rated short-circuit making current (peak) | kA | 50 | 63 |
6 | Rated peak withstand current | kA | 50 | 63 |
7 | 4s thermal stability current | kA | 20 | 25 |
8 | Control circuit and auxiliary circuit, power frequency withstand voltage for 1 minute | V | 2000 | |
9 | Rated operating voltage and auxiliary voltage | AC/DC220、 DC110/48/24 |
Working environment conditions:
1.1 Ambient air temperature: Max. temperature: +45°C; Min. temperature: -40°C; Max. daily temperature difference: 25K;
1.2 Relative humidity: Daily mean is not greater than 95%, and monthly mean is not greater than 90%;
1.3 Altitude: Not higher than 2000m;
1.4 Wind: Not exceed 35m/s (equivalent to air pressure 700Pa);
1.5 Pollution grade: Grade IV;
1.6 Radial thickness of ice: 10mm;
1.7 Earthquake resistance: horizontal acceleration: 0.3g/s2; vertical acceleration: 0.2g/s2;
1.8 Installed in places free of fire, explosion, chemical corrosion and frequent severe vibration.
1.1 Suitable for three-phase AC 50Hz, 35kV power system for ...
ZN63A-24 indoor high voltage AC vacuum circuit breaker (here...
1.1 Suitable for switching various loads with different prop...
1.1 The three-phase AC 50Hz outdoor switchgear is suitable f...
Here you can send us an inquiry concerning general questions
about TENGEN.
Our site uses cookies to provide you with a better onsite experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie Policy.
I Accept