TGQ1N series automatic transfer switch is suitable for three-phase four-wire dual power supply network with AC current 50Hz, rated working voltage of AC400V, rated working current up to 800A, to automatically connect one or more load circuits from one power supply to another, ensuring the normal power supply of the load circuit. This product is suitable for industrial places, commercial places, residential buildings and other important places.
This product complies with standard IEC 60947-6-1.
Working environment conditions:
1.1 Ambient air temperature: the ambient air temperature shall be not higher than +40ºC but shall not lower than -5ºC, with the average temperature within 24h not exceeding +35ºC;
1.2 Altitude: The altitude of the installation site should be not more than 2,000m;
1.3 Atmospheric conditions: the relative humidity of atmosphere shall not exceed 50% at the maximum ambient temperature of +40ºC, and a higher relative humidity is allowed at the lower temperature. For example, the relative humidity can reach 90% at +20ºC. Special measures shall be taken for occasional condensation due to temperature changes.
1.4 Pollution class: The pollution class of 63 frame is Level 2; the pollution class of 125 and above frames is Level 3.
1.5 Installation category: IV.
1.6 Inclination of installation: The product is fixed and installed in the cabinet, with the maximum inclination of ±22.5°.
Model | TGQ1N-63 | TGQ1N-125 | TGQ1N-160 | TGQ1N-250、320 | TGQ1N-400、630 | TGQ1N-800 | |
Standards | IEC60947-6-1 | ||||||
Executive circuit breaker | TGB1N-63 | TGB3H-63 | TGM1N-125 | TGM1N-160 | TGM1N-250、320 | TGM1N-400、630 | TGM1N-800 |
Current specifications (A) | 10、 16、 20、 25、 32、40、 50、 63 | 16、 20、 25、32、 40、 50、63、 80、 100、125 | 100、 125、140、 160 | 160、 180、200、 225、250、 280、300、 315、 350 | 250、 315、350、 400、500、 630 | 630、 700、800 | |
Rated working voltage (Ue) | AC400V 50Hz | ||||||
Rated insulation voltage (Ui) | AC 500V | AC 800V | |||||
Rated impulse withstand voltage (Uimp) | 4kV | 8kV | |||||
Pole number | 3P/4P |
TGW1N series Air Circuit Breaker is suitable for distributio...
TGM3 series moulded case circuit breaker is one of the new c...
TGB1N-40 Miniature Circuit Breaker is mainly used in the AC ...
TGBGLB-63 series residual current circuit breaker with overc...
TGB3(H)-63 Miniature Circuit Breaker is used in the 50/60Hz ...
Here you can send us an inquiry concerning general questions
about TENGEN.
Our site uses cookies to provide you with a better onsite experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie Policy.
I Accept