TGW1N series Air Circuit Breaker is suitable for distribution network with AC 50Hz, rated voltage of AC380V-AC690V, rated current of 200A-6,300A. It is used for distributing electric energy and protecting circuits and power units from overload, short circuit, undervoltage, one-phase ground or residual current.
International Standards and Certification: CE CB
Comply with the standards: IEC/EN60947-2
1. Installation category
Class IV for main circuits of the circuit breaker and voltage tripper coil and primary coil of power transformer; Class III for auxiliary circuit and control circuits. The inclination with the vertical plane does not exceed 5° when installation.
2. Pollution class: 3
3. Altitude ≤2,000m, derating when above 2,000 m.
4. Atmospheric conditions
The relative humidity does not exceed 50% at the ambient temperature of +40°C, and a higher relative humidity at the lower temperature may be allowed;
The relative humidity at the low temperature +25°C can be up to 90%. The necessary measures can be taken for condensation on the product surface due to temperature changes.
5. Protection level IP20 for the front and IP00 for the remaining
6. Electromagnetic interference Suitable for electromagnetic environment
Basic parameters | ||||||||||||
Frame current | 1600 | 2000 | 2500 | 3200 | 4000 | 6300 | ||||||
Rated working voltage Ue(V) | AC415/690 | AC400/690 | ||||||||||
Rated insulation voltage Ui(V) | 1000 | |||||||||||
Rated impulse withstand voltage Uimp(kV) | 12 | |||||||||||
Frequency (HZ) | 50 | |||||||||||
Use category | B | |||||||||||
Pole number | 3P/4P | 3P | 3P/4P | |||||||||
Maximum continuous current of N pole (A) | 100%In | / | 50%In | |||||||||
Full-breaking delay time without addition (ms) | ≤30 | |||||||||||
Closing time (ms) | ≤70 | |||||||||||
Flashover distance (mm) | 0 | |||||||||||
Rated current In(A) | 200/400/630 800/1000 1250/1600 | 200/250/400 500/630/800 1000/1250 1600/1900 2000 | 630/800 1000/1250 1600/2000 2500 | 2000/2500 2900/3150 3200 | 4000 | 4000/4900 5000/5900 6300 | ||||||
Breaking capacity | ||||||||||||
Breaking capacity | Conventional | H | Conventional | H | Conventional | H | Conventional | H | Conventional | H | —— | |
Rated ultimate short-circuit breaking capacity Icu(kA) | AC400V | 50 | 55 | 80 | 90 | 100 | 100 | 100 | 100 | 100 | 100 | 120 |
AC690V | 25 | 30 | 50 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 75 | |
Rated operating short-circuit breaking capacity Ics(kA) | AC400V | 42 | 50 | 80 | 90 | 80 | 100 | 80 | 100 | 80 | 100 | 100 |
AC690V | 20 | 25 | 40 | 65 | 50 | 65 | 50 | 65 | 50 | 65 | 65 | |
Rated short-time withstand current Icw(kA)/1s | AC400V | 42 | 50 | 55 | 65 | 80 | 80 | 80 | 80 | 80 | 80 | 100 |
AC690V | 20 | 25 | 40 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 65 | |
Rated short-time withstand current Icw(kA)/0.5s | AC400V | / | / | / | 75 | / | 100 | / | 100 | / | 100 | / |
AC690V | / | / | / | 65 | / | 65 | / | 65 | / | 65 | / |
TGM1N series moulded case circuit breaker is a new type of c...
TGM3 series moulded case circuit breaker is one of the new c...
TGQ1N series automatic transfer switch is suitable for three...
TGQ1NP series automatic transfer switch is suitable for two-...
HR17N series fuse disconnector switch is used in AC low-volt...